Load Table

PANEL

8″ RIB

LIVE LOAD

20 PSF

30 PSF

40 PSF

50 PSF

SPAN

ROOF

WALL

ROOF

WALL

ROOF

WALL

ROOF

WALL

20
190 lbs/sq

1

8′-4″

9′-2″

6′-11

7′-11″

6′-0″

6′-10″

5′-5″

6′-1″

2

8-0

9-8

6-8

7-11

5-9

6-10

5-2

6-1

3

8-11

10-10

7-5

8-10

6-6

7-8

5-10

6-10

22
161 lbs/sq

1

7-8

8-4

6-4

7-2

5-6

6-2

5-0

5-6

2

7-3

8-9

6-0

7-2

5-3

6-2

4-9

5-6

3

8-2

9-9

6-9

8-0

5-10

6-11

5-3

6-2

032
51 lbs/sq

1

5-0

4-1

3-6

3-2

2

5-0

4-1

3-6

3-2

3

5-7

4-6

3-11

3-6

040
64 lbs/sq

1

6-2

5-0

4-4

3-10

2

6-2

5-0

4-4

3-10

3

6-10

5-7

4-10

4-4

Notes – Steel

  1. Roof loads are for positive loads only and are in addition to weight
    of panel.
  2. Other gauges of steel and aluminum are available upon inquiry.
  3. Maximum allowable stress for Grade A (F) = 20,000 PSI for roofs
    and 26,667 PSI for walls where wind is the only load.
  4. Loads and spans for carbon steel are based on the AISI Cold Formed
    Steel Design Manual.
  5. Other gauges of steel may be available upon inquiry.

Notes – Aluminum

  1. Roof loads are for positive loads only and are in addition to weight
    of panel.
  2. Other gauges of steel and aluminum are available upon inquiry.
  3. Maximum allowable stress (FC) = 15,000 PSI, (FT) = 17,000 PSI for
    roof and side wall. Stresses have been increased 1/3 for wind loading.
  4. Loads and spans for aluminum are based on Aluminum Formed Sheet
    Building Sheathing Design Guide.